Pulse-Type interference suppression based on an improved wavelet threshold for wideband partial discharge detection in transformers

Guanghu Xu 1,2, Qingchuan Zhang 1,2, Gang Chen 1,2, Zhongqiang Zhan 1,2, Dandong He 1,2

1Xinjiang Key Laboratory of Extreme Environment Operation and Testing Technology for Power Transmission & Transformation Equipment, Urumqi, China
2State Grid Xinjiang Electric Power Company Electric Power Research Institute, Urumqi, China

Abstract

Pulse-type interference at high-voltage (HV) and ultra-high voltage (UHV) transformer sites severely limits the effectiveness of partial discharge (PD) detection, as conventional pulse current measurement below 1 MHz leaves 12-pulse ripple, corona, and electronic switching pulses overlapping with genuine PD signals in both time and frequency domains. This work develops an improved wavelet threshold method tightly integrated with a wideband detection platform featuring a 150 kHz to 60 MHz signal conditioning bandwidth coupled with a 3–50 MHz high-frequency current transformer (HFCT) sensor. A continuously differentiable threshold function with adjustable factor α is constructed to bridge hard and soft thresholding, a layer-dependent adaptive estimator replaces the universal threshold to match noise variance at each decomposition level, and a time-frequency cumulative energy function performs pulse pre-localization before discrimination. Validation on 500 simulation samples, 320 laboratory records from a 220 kV physical platform, and 180 field signals from three substations shows an average SNR gain of 9.3 dB, combined fitness F of 2.38 at 5 dB input SNR (F is a figure of merit balancing noise suppression and waveform preservation), and laboratory identification rates of 95.2%, 93.6%, and 94.3% for the three interference categories. Pooled field detection accuracy reaches 93.7%, feature-parameter recovery errors stay within 8.1%, and single-record processing settles at 52 ms. Pilot deployments reduced the detection blind zone from 6%–8% down to 2.5%–3%. These findings demonstrate the practical value of the proposed method for improving the reliability of online insulation condition assessment in harsh substation environments.

Keywords

Partial discharge; Improved wavelet threshold; Pulse-type interference suppression; Power transformers; High-frequency current transformer (HFCT); Denoising

Cite this article as: 

Share This Article
LinkedIn
X
Facebook
journal cover
News & Upcoming Events